JavaScript seems to be disabled in your browser. For the best experience on our site, be sure to turn on Javascript in your browser.
Adequate inventory
Bulk Purchase Discounts
Sold: 167392
Sold: 9823
Sold: 7921
Sold: 5329
Sold: 4376
Brand name:Daikin
Model number:JT170G-K
Price:Inquiry for discount
Packaging:Wooden Box / Carton
Delivery time:7~14 days (About)
Warranty:1 Year
Parameter details:Download PDF
Payment methods:Consulting support, including your preferred payment methods.
Quick Quote
Product Description
Parameter
Brand:
DAIKIN
Voltage:
200V 50Hz
Refrigerant:
R410A
200-220V 60Hz
Model:
JT170G-K
Power:
Three phase
Origin:
Thailand
REF.Oil:
Daphne FVC68D
Specifications:
Brand new
MFG.NO:
51017260 20200512
Type:
Refrigeration compressor
DP.AP:
H 4.0MPa L4.0Mpa
Application range:
Refrigeration parts
SP:
12.0MPa
Material:
Stainless steel
1. Check whether the refrigerating oil of the original compressor is too dirty. If the oil is too dirty, the system must be cleaned with nitrogen and the dry filter must be replaced. 2. Check whether the contacts of the compressor operation control AC contactor are stuck or have poor contact, causing the compressor to run out of phase. If the compressor is damaged in the coil winding, the AC contactor of the same model must be replaced. 3. Check and protect the circuit. The high and low pressure switch is in the closed state in the normal refrigerant compression state, the high pressure limit is less than or equal to 2.2Mpa, and the low pressure is more than or equal to 0.28Mpa. 4. Check whether the radiator is too dirty and must be cleaned. 5. Check whether the original equipment has refrigerant pressure, and repair it if the refrigerant is leaking.
1. Disconnect the power supply. 2. Disassemble the compressor and check its old compressor. 3. Nitrogen cleaning system, steps, disassemble the filter and blow in nitrogen from the inlet of the radiator, discharge from the outlet of the radiator, then blow in from the inlet of the filter, release from the return pipe of the compressor, and repeat cleaning several times. 4. Install the new compressor and weld the new filter. 5. Use nitrogen to pressure, 2.0Mpa pressure for leak detection for 30 minutes. 6. Circuit check and replace damaged parts, check power supply and control circuit. 7. Clean the radiator. 8. Vent the nitrogen and evacuate for 30 minutes. 9. Add the same type of refrigerant 10. Power-on debugging, check the compressor current and voltage, the normal pressure of the refrigerant, high pressure 1.7Mpa, low pressure 0.45Mpa, the refrigerant charge is expected to be 0.7kg/hp (10-30hp).
Q: What means of transportation?
A: It can be shipped by air to the nearest international airport or by courier like DHL, TNT to your address; if it's not urgently required, they can also be shipped by sea to the nearest sea port.
Q: How long is your delivery time?
A: Usually, if it is in stock, it will take 5 to 10 days. Or, if there is no stock, it is 15-20 days, depending on the quantity.
Since its establishment in 1924, Daikin has developed into a comprehensive manufacturing enterprise spanning multiple fields such as air-conditioning, fluorine chemistry, and hydraulic machinery. Especially in the field of air conditioning, it is a professional enterprise integrating R&D, production, sales and service of air conditioners, refrigerants and compressors.
Enjoy 10% off shipping on orders of 50+ pieces, or 20% off on orders of 200+ pieces.Estimated Delivery: 1-2 weeks (subject to actual situation).
After-Sales guaranteeReturns and exchanges within 30 days require the item to be unused, undamaged, and in its original packaging.
Shopping safety24/7 Online SupportSecure PaymentProtected LogisticsPrivacy Guarantee
Factory AddressPengzhou, Chengdu, Sichuan, ChinaPhnom Penh, CambodiaNaypyidaw, Myanmar